To determine whether a three-phase motor is in good condition, you can check from both electrical and mechanical aspects

To determine whether a three-phase motor is in good condition, you can check from both electrical and mechanical aspects. The specific methods are as follows:

Electrical Aspects

1. Measuring Insulation Resistance

Use a 500V megohmmeter to measure the insulation resistance of the three-phase windings to the ground (motor housing) and between phases. The resistance value should be ≥ 0.5 megohms. If it is lower than 0.5 megohms, there may be insulation damage; if it is close to 0, the motor is already damaged. During measurement, ensure the motor is powered off and grounded, and discharge the motor after each measurement.

2. Measuring DC Resistance of Windings

Use a multimeter or a single-arm bridge to measure the DC resistance of the three-phase windings. The DC resistance values of the three phases should be basically equal (with a deviation ≤ 5%). If the resistance of a certain phase is significantly lower, there may be an inter-turn short circuit; if the resistance is 0 or infinite, it indicates an open circuit or short circuit in the winding.

3. Checking No-Load Current

When the motor is running under no-load, the current is generally 10% to 50% of the rated current. If the no-load current is too high or too low, it may indicate a fault in the motor (such as bearing jamming, winding problems, etc.).

Mechanical Aspects

1. Checking Bearings

Manually rotate the motor shaft; it should rotate flexibly without jamming, abnormal noise, or unusual resistance. If the bearing is worn, lacks oil, or seizes, it may cause the motor to overheat or even burn out.

2. Checking the Fan and End Covers

Check if the fan is loose or damaged, and if the end covers are installed firmly. A faulty fan may affect heat dissipation, and loose end covers may pose safety hazards.

Notes

  • Before measurement, power off the motor and ensure it is discharged to avoid the risk of electric shock.
  • If the motor has not been used for a long time or is damp, it must be dried first before measuring the insulation resistance.
  • If there is a suspicion of inter-turn short circuit or phase-to-phase breakdown in the motor, the motor needs to be disassembled for further inspection.


Through a comprehensive judgment using the above methods, you can initially determine whether the three-phase motor is normal. If an abnormality is found, it is recommended to contact professional maintenance personnel for further inspection and repair.